EtherNet/IP (CIP over Ethernet — Rockwell/Allen-Bradley default) showing module fault, connection timeout, or I/O not coming up in Logix is usually IP/subnet, RPI, duplicate IP, EDS/AOP or switch/multicast — rarely a faulty module.
Quick distinction: EtherNet/IP I/O uses implicit (UDP, class 1) at the RPI; messaging/HMI uses explicit (TCP). If I/O drops but ping still works → suspect RPI/multicast/config, not a broken link.
Common causes
- Wrong IP / subnet — device on another subnet, wrong gateway, DHCP changed the IP.
- Duplicate IP — two devices share an IP → intermittent.
- RPI too small / overload — a low RPI floods the CPU/switch.
- EDS / AOP — missing the correct EDS or Add-On Profile version for the module.
- Switch & multicast — an unmanaged/non-IGMP switch floods multicast; or blocks ports.
EtherNet/IP module keeps faulting in Logix?
Send: the controller (CompactLogix/ControlLogix), the failing module, the fault code, the IP plan. Get a diagnosis direction.
Step-by-step diagnosis
- Ping & IP Ping the device; verify IP/subnet/gateway are correct, no duplicate IP in the range.
- Read the module fault In Logix, read the connection error code (e.g. 16#0204 timeout) for direction.
- Check the RPI Set a sensible RPI (not too small); check total packet load on CPU/switch.
- EDS / AOP Install the right EDS/AOP for the module + firmware; firmware mismatch often causes connection faults.
- Switch & multicast Use a managed switch with IGMP snooping; check VLAN/ports; avoid unmanaged on large networks.
- Capture traffic Wireshark + CIP dissector to view the connection request/response, separating config from physical faults.
⚠️ Changing IP/network config on a running system can drop I/O suddenly → ensure the machine is in a safe state first.